Home > Power Cables > How to Choose why tan delta test is required?

How to Choose why tan delta test is required?

Author: Ingrid

Aug. 12, 2024

48 0

What is principle of tan delta? What are its various Modes. - KPM

What is the Tan Delta Test?

Hengfeng supply professional and honest service.

A pure insulator when is connected across line and earth behaves as a capacitor. In an ideal insulator, as the insulating material which acts as dielectric too, is 100 % pure, the electric current passing through the insulator, only have a capacitive component. There is no resistive component of the current, flowing from line to earth through the insulator as in ideal insulating material, there is zero per cent impurity.

In a pure capacitor, the capacitive electric current leads the applied voltage by 90o.

In practice, the insulator cannot be made 100% pure. Also due to the aging of insulators, the impurities like dirt and moisture enter into them. These impurities provide the conductive path to the current. Consequently, an electric leakage current flowing from line to earth through the insulator has a resistive component.


Hence, it is needless to say that, for a good insulator, this resistive component of the electric leakage current is quite low. In another way, the healthiness of an electrical insulator can be determined by the ratio of the resistive component to the capacitive component. For a good insulator, this ratio would be quite low. This ratio is commonly known as tanδ or tan delta.

Sometimes it is also referred to as the dissipation factor.



Thus, tan δ = IR/ IC

NB: This δ angle is known as the loss angle.



On which instruments Tan Delta testing can be done?


Tan δ testing can be done on various power types of equipment used in substations like transformers, winding, current transformer, potential transformer, transformer bushing, cables, generators. It is performed to assess the quality of insulation and is performed in combination with various test likeTTR, WRM, etc.


Reasons for doing Tan δ testing?


The main purpose of the tan delta test is to make sure of maintaining a secure and reliable functioning of the transformer. The calculation of dissipation factor and capacitance values provides the result of insulation behavior of bushings and in windings too.


Variation in the capacitance value, for instance, indicates partial kind of breakdowns in bushings and automated movement of windings. Insulation deprivation, aging of the equipment, enhancement in the energy levels is transformed into heat. The amount of losses in these is calculated as the dissipation factor.

With the tan delta testing method, one can easily know the dissipation factor and the capacitance values at the required level of frequencies. So, any kind of aging factor can be identified earlier and the corresponding action can be implemented.

As we know that 'Transformers' plays a very crucial part in power, so, first of all, will discuss Tan Delta Testing in Transformers.



Tan Delta Testing Process

The below process explains the method of tan delta testing in a step-by-step manner


  • The requirements necessary for this test such as cable, potential transformer, bushings, current transformer, and winding on which this testing is conducted has to be initially separated from the system.

  • The minimal frequency level of test voltage is applied along with the equipment where the insulation to be analyzed.

  • At first, normal voltage levels are applied. When the tan delta values are as expected at this voltage level, then the applied voltage level is increased by 2 times as of applied voltage.

  • The values of the tan delta are recorded by the tan delta controller.

  • To the tan delta calculating component, a loss angle analyzer is connected which compares tan delta values at higher and general voltage levels and delivers accurate results.

It has to be noted that the testing procedure to be carried out at very minimal frequency levels.


It is more recommended to conduct testing at minimal frequency levels, because when the applied voltage level is more, then the capacitive reactance of the insulator device reaches very minimal, therefore the capacitive element of the current reaches more. As the resistive element is practically constant; it is based on the applied voltage level and the insulator's conductivity value.

Whereas at increased frequency level the capacitive current, is more, and then the amplitude of the vector amount of both the capacitive and resistive elements of the current reaches very high. So, the necessary level of power for the tan delta test would become more that seems to be not acceptable. Because of this, the power constraint for dissipation factor analysis, very minimal frequency test voltage is required.


Are you interested in learning more about why tan delta test is required? Contact us today to secure an expert consultation!


What are the Different Modes of the Tan Delta Test?

When it comes to the tan delta test, there are essentially three modes of power factor testing. Those are


  • GST Guard ' This calculates the amount of current leakage to the ground. This method eliminates the current leakage through red or blue leads. Whereas in UST, the ground is termed to be guard because grounded edges are not calculated. When the UST method is applied to the device, then the current measurement is only through blue or red leads. The current flow through the ground lead gets automatically bypassed to the AC source and thus excluded from the calculation.

  • UST Mode ' This is employed for the calculation of insulation in between ungrounded leads of the equipment. Here the individual portion of isolation has to be separated and analyze it having no other insulation connected to it.

  • GST Mode ' In this final mode of operation, both the leakage pathways are calculated by the test apparatus. The current, capacitance values, UST, and GST guards, loss in watts need to be equal to the GST test parameters. This provides the entire behavior of the test.

When the summing value of GST Guard and UST is not equal to the GST parameters, then it can be known that there is some crashing in the test set, or might the test terminal are not correctly designed.


On the whole, this is a detailed explanation of the Tan Delta Test. Here, in this article, we are completely aware of what is a tan delta test, its principle, its purpose, its methods, and its testing technique.

Also, know about what are LV to earth test, HV to earth test, and LV-HV tan delta testing methodologies and keep reading KPM Technologies 'TECH BLOG' and subscribe for different technological development in the field of power sector/ testing sector/ etc







Learn Tan delta test in 4-steps. -

Learn Tan delta test in 4-steps

 

Why Tan-delta testing is done?

 

Tan delta test is conducted for transformer oil (read here) and also for electrical equipment like C.T, P.T, Transformers ,cables etc. Purpose of this test is to determine the condition of insulation. Insulating materials (oil and paper insulation on winding) may deteriorate due to moisture ingress, aging, mechanical stress etc. Identifying the condition of insulation is important to prevent outage of equipment, breakdown time, and potential hazards.

In most of the equipment used in high voltage system tan-delta point is in-built in the equipment for conducting this test. It is located usually in box placed on outer side/cover of the equipment. Tan delta point looks like a small nail and this point is covered by a cap which grounds it.The cap is removed for testing purpose only and it is again tightened after testing is completed.

This test measures the tangent (tan) of the angle(δ) between the resistive and reactive components of the insulation impedance.

Tanδ =  (IR /IC)

How tan-delta test is conducted?

 

It is conducted using a tan-delta test kit. The kit runs on single phase AC supply, there are two leads which comes out of this testing kit, one is called H.V lead and other is called feedback lead.

Let us understand the testing process in step wise manner :

1.Equipment to be tested should be first disconnected by removing of jumper conductors, its insulator should be cleaned using a clean and wet cloth. Tan-delta point of the equipment must also be cleaned. It should be checked that there is no moisture in the tan-delta point area, if there is some moisture it should be dried completely using a blower. No moisture should be present in any of the test cables also, else the readings will not be accurate. Water should not be used for cleaning of Tan-delta point, it can be cleaned using petrol.

 

Importance of cap/cover of tan-delta point:

 

>In case of tan-delta testing of bushings of transformer, it should be ensured that tan-delta cap/cover of all remaining bushings other than being tested should be properly closed so that it gets grounded. If any cap remains open or ungrounded tan-delta readings will not be accurate. After testing of particular bushing is completed, its cap must be tightened. In case we forget to tighten the cap of tan-delta point of CT/PT, bushings, CT and charge the equipment ,it may result in damage of the equipment.

2.Kit should be properly grounded for safety purpose. For testing of equipment other than transformer winding, HV lead of the kit is connected to primary side of the equipment ,from HV lead of the kit , test voltage is injected in the equipment and feedback lead is connected to tan-delta point which is usually located inside secondary terminal box or on outer cover of the equipment.

3.We take readings of tan delta at different voltage levels, usually at 2kv, 5kv and 10kv ,the kit also calculates capacitance of the equipment. For an ideal insulator as the insulating material is 100 % pure, the current passing through the insulator should only have capacitive component and it should behave like a pure capacitor, but practically some amount of impurity is always there so there is also resistive component of current.

4.We consider a value of tanδ less than 0.7% to be good and acceptable.This test is conducted after specific time and present and previous results are compared, the tan delta value degrades year by year due to various reasons. Below is sample tan delta test report conducted on a power transformer. For taking tan-delta of bushings UST mode is used and for taking reading of windings wrt to earth GST mode is used.

 

Common observation of above sample test reuslts:

 

>Tan-delta and capacitance value at all test voltage levels should be almost equal. If it is not almost equal then some error has occurred in testing. If the result is on higher side then it should be higher for all test voltage levels. This can't happen that readings are good for one voltage level and very poor for other test voltage.

 

Test modes

 

There are different modes given in the testing kit which are used for different purpose.

UST-Ungrounded Specimen test mode: Used for measurement of insulation in between ungrounded leads of the equipment. This mode is used when we have to test CT,CVT or Bushings.

GST-Grounded specimen test mode: In this mode readings are taken wrt to ground. This mode is used when object under test is permanently grounded. For taking readings of Hv-E and LV-E of transformer windings ,we take readings in GST mode.

GSTg-Guarded GST mode: It is used to measure the stray capacitances and separating them from basic measurement in GST mode.

GSTg=UST+GST

 

What should be done in case the readings are on higher side?

 

Tan delta point to be cleaned using petrol and clean cloth.

Insulator part of the equipment needs to be cleaned using wet cloth.

It is to be checked that test cables should be free from moisture.

In case of transformer ,oil filtration should be done properly and good values of BDV,PPM etc should be obtained.

In case the equipment is too old and all attempts fail to give a good tan delta value, its O.E.M needs to be consulted.

Connection for tan delta test of transformer has been explained here.

 

FAQs:

 

What does the Tan Delta value indicate?

The Tan Delta value provides information about the quality of the insulation. Higher tan δ values suggest poorer insulation, while lower values indicate better insulation condition.

When is the Tan Delta Test typically performed?

The test is performed during the manufacturing, commissioning, and maintenance of electrical equipment, as well as during routine diagnostic assessments to monitor the condition of insulation over time.

What are the applications of the Tan Delta Test?

The Tan Delta Test is commonly used for assessing the condition of power cables, transformers, bushings, circuit breakers, and other high-voltage equipment with insulating materials.

What are the advantages of the Tan Delta Test?

Early Detection: It can detect insulation problems in their early stages, allowing for timely maintenance and preventing catastrophic failures.

What are acceptable Tan Delta values?

The acceptable Tan Delta values vary depending on the type of equipment and insulation material. Generally, lesser values than 0.7% indicate better insulation quality. Acceptable values should be defined by equipment standards or manufacturer guidelines.

Is it necessary to perform the Tan Delta Test regularly?

Regular testing is recommended, especially for critical equipment, as it helps to track the insulation's condition and plan maintenance activities accordingly.

Can the Tan Delta Test be used for oil-filled equipment?

Yes, the Tan Delta Test is commonly used for assessing the insulation condition of oil-filled transformers and bushings, where it helps identify issues like moisture or contamination in the oil.

How this Test is conducted on site?

On-site testing involves using specialized test kit that applies high voltage at a specific frequency to the equipment under test, measuring the phase angle difference between current and voltage. The results are then compared to reference values.

Can this Test predict the remaining lifespan of equipment?

While the Tan Delta Test provides valuable data about insulation condition, it cannot predict the exact remaining lifespan of equipment. It helps in making informed decisions regarding maintenance and repair.

Is it safe to perform this Test on energized equipment?

No, it is not safe to perform on energized equipment. The equipment being tested should be properly de-energized and grounded to ensure the safety of the testing personnel.

 

We insist on offering premium quality creation with very good company concept, honest product sales along with the finest and fast assistance. It will bring you not only the premium quality item and huge profit, but the most significant is to occupy the endless market for tan delta tester,tan delta test kit,ground resistance tester,earth ground testers,earth resistivity tester,ground resistance meter,high voltage insulation tester,Insulation Resistance Tester,insulation resistance meter,Surge Arrester Leakage Current Analyzer

Contact us to discuss your requirements of 240V Lightning arrester leakage current tester. Our experienced sales team can help you identify the options that best suit your needs.

Comments

0